North America / Commercial & demonstration

Ramea Newfoundland Microgrid

Organizations, planners, suppliers, equipment, controls, and reported system specifications—with source-level citations.

CoverageDetailed public record
Named organizations5
System facts17
Sources reviewed3
Last researched2026-07-19

Ramea's isolated power system evolved from a wind-diesel installation into a 2007–2011 wind-hydrogen-diesel research initiative. A peer-reviewed open-access engineering paper supplies rare component-level detail—including Caterpillar diesel ratings, Windmatic turbine generator sizes, capacitor banks, dump load, and governor modes—while the provincial record defines the later hydrogen scope.

Research status
Historical wind-hydrogen research configuration; current hydrogen-system operation is not claimed
Historical classification
Community
Reported capacity
110 kW
Coordinates
47.51927, -57.39502
Evidence note: “Every company” cannot be proven from public material alone. This page lists every organization found in the recovered record and reviewed sources, preserves unknown roles, and explicitly marks undisclosed controller or equipment details.

Project delivery

Who was involved in Ramea Newfoundland Microgrid?

5 publicly identified organizations. Where a recovered source named a participant without explaining its work, the role remains explicitly unspecified.

Organization

Caterpillar

Diesel generator manufacturer [3]

Organization

Environment Canada

Operating-data contributor acknowledged by the engineering study [3]

Organization

Frontier Power Systems

Participant named in the recovered project record; precise contractual role was not recovered [1]

Organization

Newfoundland and Labrador Hydro

Project proponent, isolated-system owner, and operating-data provider [2][3]

Organization

Windmatic

Wind turbine manufacturer [3]

System evidence

Reported capacity and specifications

Values can describe different project phases or components. Source citations are attached to each figure so discrepancies remain visible.

KW Wind
110 [1]
Diesel generation
Three 925 kW, 4.16 kV, 1,200 rpm generator sets [3]
Original wind plant
Six Windmatic WM15S turbines; each carries 65 kW and 13 kW induction generators [3]
Later wind addition described by paper
Three 100 kW wind turbines [3]
Controllable dump load
200 kW [3]
Reactive compensation
Six 30 kvar capacitor banks [3]
Typical load
Approximately 650 kW average; reported winter peak up to 1.1 MW [3]
Hydrogen project period
2007–2011 research initiative [2]

Controls and hardware

Equipment and controller details

Manufacturer and model are shown only when a source names them. Generic descriptions are not converted into guessed product assignments.

01

Diesel generator sets

Caterpillar — D3512 / 3512

Three 925 kW, 4.16 kV units at 1,200 rpm with AVR and governor controls; the paper also identifies the 1,400 hp 3512 engine family. [3]

02

Wind turbines

Windmatic — WM15S

Six machines, each with 65 kW and 13 kW induction generators. [3]

03

Diesel master control

Model not publicly disclosed

Coordinates multiple gensets operating with speed-droop and isochronous governor modes; a commercial controller model is not given. [3]

04

Hydrogen system

Model not publicly disclosed

Electrolyser, three storage tanks, and an internal-combustion hydrogen generator were within the provincial research scope; manufacturers and model numbers are not disclosed on the cited project page. [2]

Recovered detail

Additional technical notes

Concise system facts recovered from the historical project record. Treat these as historical unless a newer primary source confirms them.

  • Management

    • Community load 250 kW – 1,000 kW [1]

  • Generator control

    Automatic voltage regulators and governor controls support droop and isochronous operation, with a diesel master controller coordinating unit commitment. [3]

  • Wind integration

    The original induction-generator wind plant used six switched 30 kvar capacitor banks and a 200 kW controllable dump load for isolated-grid operation. [3]

  • Research boundary

    The paper's 150 kW pumped-hydro system is a modeled proposal, not documented installed equipment, and is deliberately excluded from the equipment list. [3]

  • Hydrogen configuration

    Provincial filings describe wind-powered electrolysis, hydrogen storage, and later electricity production through an internal-combustion hydrogen generator. [2]

Provenance

3 sources

Primary owner, government, university, supplier, and engineering sources are preferred. Archived references preserve claims whose original pages moved or disappeared.

  1. [1]
    Recovered Microgrid Projects record

    Internet Archive · Archived source · captured 2021-04-20

  2. [2]
    Ramea Wind-Hydrogen Diesel Project

    Government of Newfoundland and Labrador · Primary source

  3. [3]
    Increasing wind energy penetration level using pumped hydro storage in island micro-grid system

    International Journal of Energy and Environmental Engineering · Primary source